Cable lines - safety / 21.08.2025

Ungrounded cable screen

Before putting the cable line into operation (and then periodically during operation), the integrity of the outer sheath of cables should be checked. The procedure consists of the following steps:1️⃣ Disconnect the line from the network (if it was in operation).2️⃣ Disconnect the SVLs from the link boxes.3️⃣ Unground cable screens at both sides of

Read More
Cable lines - safety / 09.06.2025

Cable line transition tower damages

One of the weak points of cable lines is cable joints and terminations. Despite all the efforts of specialists who develop and install the joints/terminations, there are still many damages. The consequences of damage will vary depending on the location features. There are at least the following typical locations:1️⃣ Joints in the ground.2️⃣ Joints in

Read More
Cable lines - safety / 29.11.2024

Cable overheating

Single-core cables of medium voltage 6-35 kV often have simple grounding of the screens on both sides (“solid bonding”). As a result, the cable screens form closed contours, and the magnetic field of the core current induces currents in these contours, that is screen currents. Induced currents (Is) in the screens pass through the screens

Read More
Cable lines - ducts / 04.10.2024

Cable and pipe sparks

If the outer sheath of the cable is damaged, water can penetrate into the cable, and this will lead to the defects in the XLPE insulation, followed by its breakdown (that is cable will get a short circuit). Therefore, it is important to monitor the condition of the outer sheath of the cable, preventing the

Read More
Cable lines - safety / 22.08.2024

Voltage induced on cable line

Sometimes we have to lay our cable line (CL) along some other 6-750 kV existing lines (cable or overhead). In such cases, we have to think about the magnitude of the induced voltages on the core and screens of our CL. Such interference is caused by the magnetic field of currents passing in adjacent cable

Read More
Cable lines - safety / 02.02.2024

The magnetic field – it exists!

When designing cable lines, it is very rare to find such projects where there is a section of documentation in which calculations of the magnitude of the magnetic field H of the cable line would be carried out. At the same time, the magnetic field H can pose a significant danger, primarily under the following

Read More
Cable lines - safety / 15.04.2023

Safety of people in cities

The photo shows a concrete underground well. It houses cable joints for 110 kV single-core cables. There are 6 joints for 6 single-core cables, which means that there is a three-phase double-circuit cable line. A fault (short-circuit) occurred in one of joints due to poor-quality installation, which led to an explosive increase in pressure in

Read More